Rated Power Factor; Rated Motor Torque; Motor Cooling - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
r0332[3]

Rated power factor

P-Group: MOTOR
Displays power factor for motor
Index:
r0332[0] : 1st. Drive data set (DDS)
r0332[1] : 2nd. Drive data set (DDS)
r0332[2] : 3rd. Drive data set (DDS)
Dependency:
Value is calculated internally if P0308 (rated motor cosPhi) set to 0; otherwise, value entered in P0308 is
displayed.
r0333[3]

Rated motor torque

P-Group: MOTOR
Displays rated motor torque.
Index:
r0333[0] : 1st. Drive data set (DDS)
r0333[1] : 2nd. Drive data set (DDS)
r0333[2] : 3rd. Drive data set (DDS)
Dependency:
Value is calculated from P0307 (rated motor power) and P0311 (rated motor speed).
=
r0333
[Nm]
P0335[3]

Motor cooling

CStat:
CT
P-Group: MOTOR
Selects motor cooling system used.
Possible Settings:
0
Self-cooled: Using shaft mounted fan attached to motor
1
Force-cooled: Using separately powered cooling fan
2
Self-cooled and internal fan
3
Force-cooled and internal fan
Index:
P0335[0] : 1st. Drive data set (DDS)
P0335[1] : 2nd. Drive data set (DDS)
P0335[2] : 3rd. Drive data set (DDS)
Caution:
The following combination of parameter setting should not be combined:
-
P0610 = 1 and P0335 = 0 or 2 :
When P0335 = 0 or 2 the inverter cools the motor using a shaft mounted fan. If this is used in
conjunction with P0610 the cooling of the motor will be inefficient.
In essence, if the i2t calculation reduces the output frequency, then the shaft mounted fan will also reduce
its cooling effect, the motor will then eventually overheat and trip.
-
Exception:
Applications with variable torque the reduction of max. current leeds automatically to a reduction of the
load / output current.
Notice:
Motors of series 1LA1 and 1LA8 have an internal fan. This internal motor fan must not be confused with the
fan at the end of the motor shaft.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: Float
Datatype: Float
P0307
[kW ]
1000
P0311
[1/min]
π
2
60
Datatype: U16
Active: first confirm
Parameter Description
Min:
-
Unit: -
Def:
-
Max:
-
Min:
-
Unit: Nm
Def:
-
Max:
-
Min:
0
Unit: -
Def:
0
QuickComm.: Yes
Max:
3
Level
3
Level
3
Level
2
55