Vdc Controller; Configuration Of Vdc Controller - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Parameter Description
V
DC
V
DC, Chopper
Chopper
active
V
DC, act
V
DC, Chopper
200 - 240 V
V
The threshold for the warning A0535 is equivalent to 10 seconds running at 95 % duty cycle. The duty cycle
will be limited when it was running 12 seconds at 95 % duty cycle.
3.28

Vdc controller

P1240[3]

Configuration of Vdc controller

CStat:
CT
P-Group: FUNC
Enables / disables Vdc controller.
The Vdc controller dynamically controls the DC link voltage to prevent overvoltage trips on high inertia
systems.
Possible Settings:
0
Vdc controller disabled
1
Vdc-max controller enabled
2
Kinetic buffering (Vdc-min controller) enabled
3
Vdc-max controller and kinetic buffering (KIB) enabled
Index:
P1240[0] : 1st. Drive data set (DDS)
P1240[1] : 2nd. Drive data set (DDS)
P1240[2] : 3rd. Drive data set (DDS)
148
V
DC, act
100 %
∆V
V
1
0
P1237
1
Duty cycle
monitoring
0
Mains
380 - 480 V
500 - 600 V
9.8 V
17.0 V
Datatype: U16
Active: Immediately
t
t
Chopper , ON
t
t
Chopper
t
0
x
1
Alarm
A0535
21.3 V
Unit: -
QuickComm.: No
MICROMASTER 440
Issue 01/06
t
1
1
=
=
f
2000
Hz
Chopper
x
t
=
t
Chopper , ON
Chopper
100
Level
Min:
0
3
Def:
1
Max:
3
Parameter List