Inverter parameters (Modulator)

P1800

Pulse frequency

CStat:
CUT
P-Group: INVERTER
Sets pulse frequency of power switches in inverter. The frequency can be changed in steps of 2 kHz.
Dependency:
Minimum pulse frequency depends on P1082 (maximum frequency) and P0310 (rated motor frequency).
-
see derating in P1082
-
P1800 > 30 * P0310
Note:
-
If the pulse frequency is increased, max. inverter current r0209 can be reduced (derating). The derating
characteristic depends on the type and power of the inverter (see manuall OPERATING
INSTRUCTION).
-
If silent operation is not absolutely necessary, lower pulse frequencies may be selected to reduce
inverter losses and radio-frequency emissions.
-
Under certain circumstances, the inverter may reduce the switching frequency to provide protection
against over-temperature (see P0290).
r1801

CO: Act. pulse frequency

P-Group: INVERTER
Actual pulse frequency of power switches in inverter.
Notice:
Under certain conditions (inverter overtemperature, see P0290), this can differ from the values selected in
P1800 (pulse frequency).
P1802

Modulator mode

CStat:
CUT
P-Group: INVERTER
Selects inverter modulator mode.
Possible Settings:
0
SVM/ASVM automatic mode
1
Asymmetric SVM
2
Space vector modulation
Notice:
-
Asymmetric space vector modulation (ASVM) produces lower switching losses than space vector
modulation (SVM), but may cause irregular rotation at very low frequencies.
-
Space vector modulation (SVM) with over-modulation may produce current waveform distortion at high
output voltages.
-
Space vector modulation (SVM) without over-modulation will reduce maximum output voltage available
to motor.
P1803[3]
Max. modulation
CStat:
CUT
P-Group: INVERTER
Sets maximum modulation index.
Index:
P1803[0] : 1st. Drive data set (DDS)
P1803[1] : 2nd. Drive data set (DDS)
P1803[2] : 3rd. Drive data set (DDS)
Note:
-
P1803 = 100 % : Limit for over-control (for ideal inverter without switching delay).
-
For vector control the modulation limit will be reduced automatically with 4 %.
P1820[3]
Reverse output phase sequence
CStat:
CT
P-Group: INVERTER
Changes direction of motor rotation without changing setpoint polarity.
Possible Settings:
0
OFF
1
ON
Index:
P1820[0] : 1st. Drive data set (DDS)
P1820[1] : 2nd. Drive data set (DDS)
P1820[2] : 3rd. Drive data set (DDS)
Dependency:
If positive and negative revolution is enabled, frequency setpoint is directly used.
If both positive and negative revolution are disabled, reference value is set to zero.
Details:
See P1000 (select frequency setpoint)
188
Datatype: U16
Unit: kHz
Active: Immediately
QuickComm.: No
Datatype: U16
Unit: kHz
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: Float
Unit: %
Active: Immediately
QuickComm.: No
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Issue 01/06
Min:
2
Def:
4
Max:
16
Min:
-
Def:
-
Max:
-
Min:
0
Def:
0
Max:
2
Min:
20.0
Def:
106.0
Max:
150.0
Min:
0
Def:
0
Max:
1
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Level
2
Level
3
Level
3
Level
4
Level
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents