UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Issue 23 (2024-03-15)
NO TE
The UPS supports 208 V output. In the case of 208 V output, the power is derated to
90%. The cable connections and cable connections for 208 V and 200 V are similar.
Table 5-19 Output settings
Item
Description
Output
Set the system output
mode
mode. The input mode is
identified automatically
by the system. This
parameter is
configurable only after
the inverter is shut
down.
Voltage
Indicates the system
level
output voltage level.
After you change the
voltage level, the upper
threshold for bypass
voltage is restored to the
default value (15% or
20%). This parameter is
configurable only after
the inverter is shut
down.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Default Value
Value Range
This
Single–phase,
parameter is
Three-phase
not
configurable
for the 6
kVA/10 kVA
models. The
default value
is Single-
phase.
15 kVA/20
kVA: Three-
phase
6 kVA/10 kVA:
6 kVA/10 kVA:
220 V
208 V, 220 V, 230
V, 240 V
15 kVA/20
kVA single-
15 kVA/20 kVA
phase output:
single-phase
220 V
output: 208 V, 220
V, 230 V, 240 V
15 kVA/20
kVA three-
15 kVA/20 kVA
phase output:
three-phase
380 V
output: 380 V, 400
V, 415 V