UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Issue 23 (2024-03-15)
Item
Description
Power
Determine whether to enable the power
segment
segment function for a singe UPS. (This
function is not supported in a parallel
system). This parameter is configurable
only after the inverter is shut down.
Self-Load screen
Figure 5-32 Self-Load screen
Table 5-23 Self-load settings
Item
Description
Output
This parameter is used only during the
power
tests before shipment. This parameter is
ratio
configurable only after the inverter is
shut down.
Self-load
This parameter is used only during the
mode
tests before shipment. This parameter is
configurable only after the inverter is
shut down.
Others screen
Figure 5-33 Others screen
NO TE
The EPO enable setting is available only for the UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01. EPO is enabled for the UPS2000-G-6KRTS/UPS2000-G-10KRTS/
UPS2000-G-15KRTL/UPS2000-G-20KRTL by default.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Control Panel
Defau
Value
lt
Range
Value
Disabl
Disabled,
ed
Enabled
Defa
Value
ult
Range
Value
80%
20%–
100%
Disabl
Disabled,
ed
Enabled
93