Huawei UPS2000-G User Manual page 92

Lead-acid battery
Hide thumbs Also See for UPS2000-G:
Table of Contents

Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
2.
Issue 23 (2024-03-15)
Table 5-15 SNMP card settings
Item
Description
IP alloc.
Specifies the DHCP address
allocating mode. After the
allocating mode is set to
Automatic, an Allocating
dialog box is displayed on the
screen. If allocation succeeds,
the new IP address is
displayed. If allocation fails,
the IP address restores to the
default one: 192.168.0.10. If
the allocating mode is set to
Automatic, you can only
query the IP address but
cannot set the IP address
manually.
NOTE
If the optional card does not
support the DHCP function, the
allocating mode cannot be set to
Automatic on the UPS
monitoring module. You are
advised to upgrade the SNMP
card.
IP
Set an IP address for the
address
SNMP card.
Subn.
Set a subnet mask for the
mask
SNMP card.
Gateway
Set a gateway address for the
SNMP card
If a Modbus card is connected, the following parameters are displayed:
Figure 5-25 Modbus card settings
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Control Panel
Default
Value Range
Value
Manual
Manual,
Automatic
192.168.0.10
1.0.0.0–
223.255.255.2
55
255.255.255.
-
0
192.168.0.1
1.0.0.0–
223.255.255.2
55
84