Table 3-12 Backup time parameters for the ESS-240V12-9AhBPVBA01/
ESS-240V12-9AhBPVBA04 battery pack (20 kVA, calculated based on 94% battery
efficiency)
Load (%)
100%
80%
50%
30%
Figure 3-4 Backup time curve for the ESS-240V12-9AhBPVBA01/
ESS-240V12-9AhBPVBA04 battery pack (20 kVA, calculated based on 94% battery
efficiency)
Issue 23 (2024-03-15)
Load (W)
18000
14400
9000
5400
Copyright © Huawei Digital Power Technologies Co., Ltd.
Two
Four
Battery
Battery
Packs
Packs
(min)
(min)
4
12
7
17
12
32
26
57
3 Technical Specifications
Six Battery
Eight
Packs
Battery
(min)
Packs
(min)
23
32
29
44
53
70
88
125