UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Issue 23 (2024-03-15)
Item
Description
EOD
Determine whether to
auto
automatically start inverter
-
output after the mains
start
becomes normal after EOD.
This parameter is
configurable only after the
inverter is shut down.
Shut
After the UPS transfers to
dow
battery mode, the UPS shuts
n
down when the time
dela
reaches the value of this
y
parameter. If this parameter
is set to 0S, the shutdown
delay function is disabled. If
the delay time is set to
other values, ensure that
backup time is greater than
shutdown delay time of
battery mode. Otherwise,
the power supply to loads
may be disconnected. The
parameter is configurable
in non-battery mode or
non-battery ECO mode.
NOTE
● If the mains input and
bypass input use the same
power source, the system
powers off when the
shutdown delay in battery
mode reaches the preset
value. If the mains input
and bypass input use
different power sources,
the system transfers to
bypass mode when the
shutdown delay in battery
mode reaches the preset
value.
● The Bat mode shut delay
parameter is not
synchronized in a parallel
system. In a parallel
system, set this parameter
to the same value for
different UPSs.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Default
Value Range
Value
Enabled
Disabled, Enabled
0s
0–600s
The value interval is
30s. For example, the
value can be 0s, 30s,
60s, and 90s.
5 Control Panel
105