Setting Battery Parameters - Huawei UPS2000-G User Manual

Lead-acid battery
Hide thumbs Also See for UPS2000-G:
Table of Contents

Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)

5.6.3.4 Setting Battery Parameters

The configured number of batteries on the LCD must match the actual number.
When the actual number changes, update the configured number. If the
configured number is less than the actual number, the battery lifespan is
shortened. If the configured number is greater than the actual number, battery
leakage may cause a fire.
Issue 23 (2024-03-15)
Item
Description
Auto
Specifies whether to automatically check
check bus
the bus capacitance upon power-on and
capa.
generate capacitance failure warnings. If
the value is set to Enabled, the UPS
startup time takes additional 30 seconds
to 180 seconds. This parameter is
configurable only after the inverter is
shut down.
Note: This parameter is configurable only
for the 15 kVA/20 kVA UPS.
Auto start
Specifies whether to automatically start
normal mode after the UPS connects to
the mains. This parameter is
configurable only after the inverter is
shut down.
No
If this parameter is set to Disable, the No
battery
battery alarm is not reported. This
alarm
parameter automatically changes to
Enable after batteries are connected. This
parameter is configurable only when
batteries are not connected.
NOTE
If batteries are connected and you try to set
this parameter, the system displays a message
indicating that batteries are connected and this
parameter cannot be set.
EPO
Specifies whether to enable EPO. EPO is
enable
performed only when this parameter is set
to Enable and the EPO switch is triggered.
This parameter is configurable only for
the UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01.
CA UTION
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Control Panel
Defau
Value
lt
Range
Value
Enabl
Disabled,
ed
Enabled
Disabl
Disabled,
ed
Enabled
Enabl
Disabled,
ed
Enabled
Disabl
Disabled,
ed
Enabled
95

Advertisement

Table of Contents
loading

Table of Contents