Huawei UPS2000-G User Manual page 150

Lead-acid battery
Hide thumbs Also See for UPS2000-G:
Table of Contents

Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Check
Item
Battery
appearanc
e
Battery
operating
temperatu
re
Issue 23 (2024-03-15)
Expected
Result
1. The surface is
clean and
tidy without
stains.
2. The battery
terminals are
intact.
3. Batteries are
free from
damage and
cracks.
4. Batteries are
free from
acid leakage.
5. Batteries are
not deformed
or bulged.
1. The battery
ambient
temperature
is 25±5°C.
2. The battery
operating
temperature
ranges from
0°C to 40°C.
3. Battery
charge and
discharge
conditions
meet the
requirements
specified in
the battery
specifications
.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Troubleshooting
If an exception occurs,
contact technical
support.
1. Identify the cause
of an abnormal
battery operating
temperature.
2. If the fault persists,
contact technical
support.
8 Routine Maintenance
Maintenance Interval
Monthly
Monthly
142

Advertisement

Table of Contents
loading

Table of Contents