Huawei UPS2000-G User Manual page 100

Lead-acid battery
Hide thumbs Also See for UPS2000-G:
Table of Contents

Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Issue 23 (2024-03-15)
Figure 5-31 Power Segment screen
NO TE
● In single UPS mode, sL connects to primary loads and pL connects to secondary
loads.
● In single UPS mode, if the power segment function is enabled, pL is disconnected
and sL continues to supply power when an overload occurs.
● In a parallel system, connect loads to the AC OUTPUT pL terminal.
Table 5-22 Power segment settings
Item
Description
Dis. time.
pL terminal loading time in battery mode
thres.
when power segment is enabled. In
battery mode, if the discharge time
exceeds this value, the system disconnects
the loads connected to the pL terminal.
(This function is not supported in a
parallel system.) The parameter is
configurable in non-battery mode or
non-battery ECO mode.
NOTE
The 15 kVA/20 kVA UPS supports battery ECO
mode only in the case of two power sources.
In battery ECO mode, the bypass supplies
power to the UPS, and batteries are used as
backup power. If the bypass is abnormal, the
UPS transfers to battery mode.
Dis. volt.
Lower threshold of the battery voltage
thres.
when pL is allowed to carry loads in
battery mode when the power segment
function is enabled. In battery mode, if
the battery voltage is less than this value,
the system powers off the loads
connected to the pL terminal. (This
function is not supported in a parallel
system.) The parameter is configurable
in non-battery mode or non-battery
ECO mode.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Control Panel
Defau
Value
lt
Range
Value
30
0–999
min
min
2.00
1.90–2.25
V/cell
V/cell
92