6.3 Connection
Connection of the foundation grounding electrode
No.
1
Remove the screws and clamping plates of the connection terminal
2
Cut the foundation grounding electrode to the correct length
3
Clean the clamping surface of the foundation grounding electrode
4
Place the foundation grounding electrode in the clamp
5
Mount the clamping plates
6
Tighten all screws with the corresponding tightening torque from the table in the comments sec-
tion
7
Measure and write down the value of the earth loop impedance:
Screw
M5
M6
M8
M10
M12
Connection of the protective conductor
No.
1
Open the clamp for the protective conductor connection on the equipotential busbar or remove a
connection screw on the equipotential busbar
2
Cut the protective conductor to the correct length
3
Remove the sheath of the protective conductor up to the connection of the cable lug or the wire
end sleeve
4
Select a cable lug or wire end sleeve for the appropriate conductor cross-section
5
Strip the insulation from the cable end so that the remaining insulation extends up to the cable lug
or wire end sleeve
6
Fasten the cable lug or the wire end sleeve correctly to the cable end using a suitable crimping
tool
Note
Follow these instructions when using a cable lug:
• Insert a shrink-on sleeve over the cable lug. The shrink-on sleeve must extend slightly
beyond the insulation of the cable and cover the crimping point of the cable lug.
• Use a suitable tool to heat the shrink-on sleeve.
70
Checklist item
Tightening torque
5 Nm
10 Nm
20 Nm
45 Nm
75 Nm
Checklist item
Installation and Commissioning Checklist for SICHARGE
UC Product Information, 03/2023, A5E52548271-AA
P
F
N/A
P
F
N/A