SICHARGE UC MastHood
5.3 Connection
Connection of the foundation grounding electrode
No.
1
Remove the screws and clamping plates of the connection terminal
2
Cut the foundation grounding electrode to the correct length
3
Clean the clamping surface of the foundation grounding electrode
4
Place the foundation grounding electrode in the clamp
5
Mount the clamping plates
6
Tighten all screws with the corresponding tightening torque
7
Measure and write down the value of the earth loop impedance:
Connection of the protective conductor
No.
1
Remove the screw from the grounding plate
2
Cut the protective conductor to the correct length
3
Remove the sheath of the cable to connect the cable lug
4
Choose a cable lug for the appropriate conductor cross-section
5
Strip the insulation from the end of the cable so that the remaining insulation extends up to the
cable lug
6
Fasten the cable lug correctly to the end of the conductor using a suitable crimping tool
7
Screw the cable lug of the protective conductor to the ground connection
8
Tighten the screw with the corresponding tightening torque
9
Measure and write down the value of earth loop impedance:
Connection for the low voltage cable/AC
No.
1
Pull the socket out of the plug.
2
Open the socket.
3
Remove the jacket of the low voltage cable/AC to a length of approx. 5 cm.
4
Insert the connection cable into the enclosure.
5
With a flexible cable, select the wire end sleeves for the corresponding conductor cross section.
6
Strip the ends of the conductors so that the remaining insulation reaches up to the wire end
sleeve.
7
Fasten the wire end sleeves properly on the conductor ends.
8
Clamp the protective conductor into the ground terminal.
9
Clamp the L conductor into the L terminal.
10
Clamp the N conductor into the N terminal.
11
Check the connections of the conductors to the terminals.
12
Tighten the clamps with a torque of 0.25 Nm.
13
Close the enclosure of the socket.
14
Insert the socket into the plug.
50