Table F-1 on page F-1 presents the default values of the adjustable parameters after the
battery has been disconnected or after the Hydran 201Ti's embedded software has been
upgraded.
Category
Period B
Low-Low alarm
Low alarm
Gas level
High alarm
High-High alarm
Alarms delay
Trend period
Low-Low alarm
Low alarm
Hourly trend
High alarm
High-High alarm
Alarms delay
Trend period
Low-Low alarm
Low alarm
Daily trend
High alarm
High-High alarm
Alarms delay
Part 17997
Default Values of the Parameters

Table F-1 - Default Values of the Parameters

Parameter
Rev. 6, March 2011
Unit
Value
Hours
24
ppm
5
ppm
15
ppm
250
ppm
500
Minutes
10
Hours
24
ppm/period -20
ppm/period -10
ppm/period 10
ppm/period 20
% of period 33
Days
30
ppm/period -50
ppm/period -25
ppm/period 25
ppm/period 50
% of period 33
Appendix F
Status
Disabled
Disabled
Enabled
Enabled
Disabled
Disabled
Enabled
Enabled
Disabled
Disabled
Enabled
Enabled
F-1