Resetting The Hourly Trend, Daily Trend And Period B; Verifying And Setting The Temperature Parameters Of The Hydran 201; Sensor - GE Hydran 201 i Instruction Manual

Hide thumbs Also See for Hydran 201 i:
Table of Contents

Advertisement

Chapter 6 • Hydran 201Ti Installation
6.4.4

Resetting the Hourly Trend, Daily Trend and Period B

The hourly trend, daily trend and Period B are reset by changing the value of their period
and then restoring them to their initial value after five minutes. Proceed as follows:
1.
In the submenu H201Ti V2.2x;Gas, access the submenu Gas;HourlyTrend.
2.
Access the parameter HourlyTr Period.
3.
Set this parameter to 1 hour.
4.
In the submenu H201Ti V2.2x;Gas, access the submenu Gas;DailyTrend.
5.
Access the parameter DailyTr Period.
6.
Set this parameter to 1 day.
7.
In the submenu H201Ti V2.2x;Temperature, access the submenu Temper-
ature;DynOil Sampl.
8.
Access the parameter Period B.
9.
Set this parameter to 0 hour.
10. Wait five minutes and set these parameters to their default value:
• HourlyTr Period to 24 hours
• DailyTr Period to 30 days
• Period B to 24 hours
For details on trend computations and reset, see Section 10.4.2 on page 10-11.
6.4.5

Verifying and Setting the Temperature Parameters of the Hydran 201

Sensor

For details on the parameters and commands in the submenu Temperature, see
Section 4.5.3 on page 4-17.
1.
Access the submenu H201Ti V2.2x;Temperature.