5.
Push DOWN four times until Date&Time appears.
6.
Access this menu by pushing ENTER.
7.
Select Year using the DOWN or UP key.
8.
To be able to adjust this value, push CHANGE.
9.
When asked to enter the password #1 (1253), use the UP and ENTER keys.
10. Modify the value using the UP, DOWN and ENTER keys.
11. Adjust the Month, Day, Hour and Min by repeating the steps 7 to 10 above.
12. When the Date & Time is adjusted, push END.
13. To abort an operation if needed, push ESC.
6.2.4

Verifying the Alarm Relays

The steps described in this Section may be used during the Hydran 201Ti verification,
maintenance and troubleshooting procedures; certain steps may therefore not apply to your
particular situation. Perform all the prodecures (from Section 6.2.4.1 on page 6-9 to
Section 6.2.4.6 on page 6-12).
To verify the relays using the alarm contacts, connect an ohmmeter to the Alarm Contacts
9-Terminal Block (item 12 in Figure 2-5 on page 2-9). To identify each terminal, see Table
D-2 on page D-1.
6.2.4.1

Gas High Alarm

1.
Access the top of the extended menu by pushing ENTER twice (History appears).
Note: Once accessed, the extended menu times out after 30 minutes of keypad inactivity.
2.
Access the submenu H201Ti V2.2x;Relays/Analog.
3.
Access the submenu Relays/Analog;GasH Relay.
4.
Access this relay by pushing ENTER (the state of the relay is now displayed).
Part 17997
Verification of Operation Prior to Installation
Rev. 6, March 2011
6-9