12. Do not punch additional openings in the H201Ci Controller's enclosure. This
enclosure already has openings for the various cables used with the
Hydran 201i System. If additional openings must be made, apply a protective coating
to the bare metal around the hole to prevent rust.
13. Do not remove the watertight cap from unused openings of the H201Ci's enclosure.
5.2

INSTALLATION OVERVIEW

A typical installation of the Hydran 201i System is shown in Figure 5-8 on page 5-8. Here
is a description of each component:
1.
Hydran 201Ci Controller (Hydran 201Ci-C Communications Controller or
Hydran 201Ci-1 One-Channel Controller) installed on vibration-absorbing rubber
pads (Figure 1-5 on page 1-9)
2.
Full-bore gate or ball valve
3.
Hydran 201Ti Intelligent Transmitter
4.
H201Ti's supervisory link cable in a rigid or flexible steel conduit
5.
H201Ti's power supply cable in a rigid or flexible steel conduit
6.
Cable for communications and analog outputs in a rigid or flexible steel conduit
(distinct from alarm cable conduit), toward a supervisory control and data acquisition
(SCADA) system
7.
Cable for alarms in a rigid or flexible steel conduit, toward a SCADA system
8.
H201Ci Controller's power supply cable in a rigid or flexible steel conduit
All procedures in this manual must be strictly adhered to. Any
WARNING
CAUTION
deviation from these could cause irreversible damages to the
transformer being monitored and/or the Hydran 201i System, and
could lead to property damage, personal injury and/or death. Instal-
lation and maintenance of the Hydran 201i System must be carried
out by qualified personnel only.
Part 17997
Rev. 6, March 2011
Installation Overview
5-7