Table D-6 - J3 Local Analog Output Connector, J4 Isolated Supervisory Link Connector, And Termination Board - GE Hydran 201 i Instruction Manual

Hide thumbs Also See for Hydran 201 i:
Table of Contents

Advertisement

Table D-6 - J3 Local Analog Output Connector, J4 Isolated Supervisory Link Connector, and Termination Board

Terminal
Description
1
TDM pulse, output- Isolated RS-422
2
TDM pulse, output+
3
Serial data, I/O-
4
Serial data, I/O+
5
Loop supply, input- Isolated +5 Vdc
6
Loop supply, input+
4–20 mA analog
7
current, OUT+
4–20 mA analog
8
current, OUT-
Supervisory link
Sh 1
cable shield
Analog output
CFG
configuration
Part 17997
Hydran 201Ti Intelligent Transmitter
From (Internal) To (External)
Isolated RS-422
driver, J4-1 and
receiver
J4-2
Isolated RS-485
Isolated RS-485
transceiver, J4-3
transceiver
and J4-4
Isolated 15 V
regulator input,
link supply
J4-5 and J4-6
output
Current loop,
Wired by the
J3-2
user to a
Current loop,
SCADA or RTU
J3-3
Supervisory link
H201Ti chassis
cable shield
Active output:
not connected
Current loop,
Passive output:
J3-4
to the 4–20 mA
OUT- terminal 8
Rev. 6, March 2011
Comments
Must be connected
to H201Ci-1; not
used with H201Ci-C
Must be connected
to any H201Ci
Controller
Isolated power
supply built into
H201Ci Controller
4–20 mA =
0–2,000 ppm
(500 maximum)
High-frequency
grounding
See Figure D-1 on
page D-4 and
Figure D-2 on
page D-4
D-3

Advertisement

Table of Contents
loading

Table of Contents