Door Closing By Time; Miscellaneous - Panasonic EBL512 G3 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
21.1.5
21.1.6
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
 Multiple reset (default): All activated fire alarms in the system
will be reset simultaneously by pressing the "Reset" button.
 Single reset: One activated fire alarm in the system, shown in the
control unit's alphanumeric display on the first row to the left,
will be reset by pressing the "Reset" button, i.e. all activated fire
alarms have to be reset one by one. This function is a violation to
the EN54-2 standard.
 Single encapsulated reset:
function is a violation to the EN54-2 standard.
Encapsulation function: If an alarm point / zone is reset while still in
alarm state (e.g. smoke in a smoke detector or a manual call point with
a broken glass) this unit will be automatically disabled in order not to
activate a new fire alarm within 20 seconds. It will stay disabled until
re-enabled via menu H2/B5.
LED "General disablements" is indicating one or more disablement in
the system.

Door closing by time

Active: If all fire doors shall be closed at a definite time every
day, this checkbox shall be marked.
Hour: 00 – 23
Minute: 00 - 59

Miscellaneous

Use daylight saving time:
country regulations, see chapter "Daylight saving time", page 109.
Use special menu during fire alarms: Not valid for EBL512
G3.
Silence buzzer by door switch: If the buzzer in the c.i.e. shall be
silenced when the door is opened, this checkbox shall be marked
but this is a violation to the EN54-2 standard.
Enhanced disablements: Checkbox marked = Disabled alarm
points will not activate pre-warning, fire alarm or fault.
Checkbox not marked = Disabled alarm points will not activate
pre-warning or fire alarm but fault can be activated. This is a
violation to the EN54-2 standard.
NOTE! Sensor values for a disabled detector will not be saved,
i.e. only the sensor values stored before and after the disablement
will be used for the week average calculation.
Point alarm presentation: This checkbox shall be marked for an
EBL512 G3 United version 2.7.x in a mixed network.
Flash LED on MCP 3333, 3339: The manual call point's built-in
LED will flash each time the c.i.e. communicates with the call
point If this option is disabled the LED is switched off until the
call point is operated.
Local reset of fan controls: Checkbox marked = Reset of fan
control system is local, i.e. all fan control systems in the c.i.e.
where the switch is located will be reset.
134
Encapsulation function.
According to the current EU or
This