Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x

Disable outputs for routing equipment

Disabled and Re-enabled via menu H2/B9. For more information see
EBL512 G3 United version 2.7.x Operating Instructions MEW01473.
Disconnect & Re-connect loop / zone line
input
Disconnected via menu H8/S1 and Re-connected via menu H8/S2:
COM loop
Zone line input
Addr. zone interface (2335 and 3361 zone line input)
For more information see EBL512 G3 United version 2.7.x Operating
Instructions MEW01473.

External time channels

39 external time channels can be used to:
disable and re-enable alarm points
turn the Alert Annunciation function on/off
activate programmable control outputs
turn Alternative alarm algorithm for analog detector on/off
turn the 2-unit dependence function on/off
The 39 external time channels are for the whole system.
programmable input with trigger condition/type "External Time
Channel" is used for each external time channel, which also is given a
Number (15-63). The input is controlled by some external equipment,
e.g. another time system, a key switch, a timer, etc. with a normally
open contact (normally low) or a normally closed contact (normally
high). When the input is "activated" the time channel is ON.
NOTE! You must not use more than one input per time channel.
(This is checked in the "Validity check" in Win512 version 2.7.x).

Test mode

Up to four zones can be set in Test mode at the same time. Alarm
points / zones can be tested during the Monthly test via menu H1 or
separately via menu H7.
United version 2.7.x Operating Instructions MEW01473. The LED
"Test mode" on the c.i.e. front indicates one or more zones in Test
mode. Zones in Test mode are also simultaneously shown in the c.i.e.
display. Disablements, faults and fire alarms have higher priority, i.e.
the presentation of zones in Test mode will be suppressed during such
a condition. In order to shorten the testing time, any time delay before
alarm will be "turned off" in Test mode.
97
Any 2-zone / -address dependence and the function "delayed alarm" will
be ignored.
104
For more information see EBL512 G3
97
One