Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
filtering algorithms (see chapter "Functions / Services / Features",
page 84).

Self diagnosis of internal devices

The detectors perform an internal check of some vital functions and
components (e.g. the IR-LED).
message will be shown in the c.i.e.
The following is valid for the different type of detectors:
4352: This detector has no self diagnosis of internal devices.
4350: This detector has self diagnosis of internal devices (but no
separate fault output).
4301: This detector has self diagnosis of internal devices.
4300: This detector has self diagnosis of internal devices.

Address setting check

The indication LED in the detectors 4301 and 4300 will in all modes
blink every second when the detector is powered and the COM loop
address is not set with the Address setting tool 3314, i.e. as long as the
address is "000". The address should be set in the interval 001-127.
128
In some modes a separate fault