Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
The output for fire alarm routing equipment (fire brigade tx) in the
110
master will be activated
 Fire alarm in the system.
or
 Fault on the TLON network AND fire alarm activated by any
slave, which will be specially presented, see below.
or
 No fault on the TLON network AND fire alarm activated by
any slave AND no other fire alarm in the system. (In this case
also a fault will be generated, see below.)
The slave inputs in the master will be "blocked" as follows:
 No fault on the TLON network AND Fire alarm in the system.
Presentation of slave unit fire alarm
In the master, a fire alarm activated by a slave will be presented as in
the following example:
POINT: 999-02
User definable text message
The zone number "999" indicates that the fire alarm is activated by a
slave. The address "02" indicates the slave, in this example control
unit number 02. The user definable text message may be used to
indicate that the alarm originates from a CU (slave).
Presentation of slave unit fault
An open circuit (cut-off) or short circuit on the slave inputs in the
master will generate a fault and a fault message as follows (depending
on which unit is used):
FAULT:Cut-off input n,1580 board b, CU xx
FAULT:Sh-circ input n,1580 board b, CU xx
n = zone line input (0-7) on the 1580 board.
b = 1580 board no. (0-5) in the master
xx = control unit no. (00-29) of the master.
No fault on the TLON network AND fire alarm activated by any slave
AND no other fire alarm in the system will, besides the fire alarm,
generate a fault and a fault message as follows (depending on which
unit is used):
FAULT: Alarm input n,1580 board b, CU xx
n = zone line input (0-7) on the 1580 board.
114
as follows:
No.:001