Figure 10. Win512 version 2.7.x "Input" dialog boxes. Different trigger conditions
require different additional information, i.e. only the enabled fields can/shall be
filled in.
NOTE! The 3361 unit, Input 0, has a special input dialog box.
10.1
10.1.1
10.1.2
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x

Programmable inputs

In each control unit are four programmable, not supervised inputs
(I0-I3) available.
On the COM loops can be connected the addressable multipurpose I/O
unit 3361 with two programmable inputs.
Each input is programmed (via Win512 version 2.7.x), see dialog
boxes below.
The 3361 unit's Inputs In0 / Z & In1
Connections, see drawings 512 G3 – 31 and – 36.

Input In0

Input 0 can be used as a general input (In0) – like the c.i.e. inputs I0-
I3 or used as a zone line input (Z) requiring an end-of-line capacitor
(470 nF).

Input In1

Input 1 is an isolated optocoupler input requiring a NO / NC contact
and external 24 V DC (8 mA).