Disabled alarm points and outputs are indicated by LED Fault /
Disablements "General disablements" on the c.i.e. front and are listed
in menu H4/U1-U2.
Enhanced Disablement (Default) = Fire alarm, pre-warning and fault
signal cannot be activated by the disabled alarm point/zone. If only
fire alarm and pre-warning shall be disabled, "Enhanced Disablement"
shall not be selected, see chapter "Miscellaneous", page 134.
NOTE! Enhanced Disablement is NOT valid when a time channel is
used for disablements, only when menu H2/B1 or B2 is used.

Disable zone

A whole zone (all addresses within a zone, except the manual call
points) can be disabled via menu H2/B1.
H2/B4.

Disable zone / address

Individual alarm points can be disabled via menu H2/B2. Re-enabled
via menu H2/B5.
Time channels can be used to disable and re-enable automatically.

Disable control output

All outputs (except outputs of type "Alarm Device") can be
individually disabled via menu H2/B3. Re-enabled via menu H2/B6.
Disabled output will stay in (or return to) the normal condition for the
output respectively.

Disable / Re-enable output type

The control outputs can be collectively disabled via menu H2/B7,
type:
"Control (general)"
"Extinguishing"
"Ventilation"
"Control/exting./vent.
It is possible to do this for one or more specific control units or for all
control units (i.e. the whole system). Re-enabled via menu H2/B7.
Disabled outputs will stay in (or return to) the normal condition for the
output respectively.

Disable / Re-enable alarm devices

The control outputs of type "Alarm device (sounder)" can be
collectively disabled / re-enabled via menu H2/B8. Disabled outputs
will stay in (or return to) the normal condition for the output
respectively.

Disable interlocking output

Individually disabled via menu H9/C4. Re-enabled via menu H9/C5.
See also chapter "Disable interlocking output (H9/C4)", page 82.