Panasonic EBL512 G3 Planning Instructions page 47

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
9.1.1.6
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
6295 Heat detector:
detector, 57°C, class A2 S (static response temp. range 54-
70°C), latching.
Min./typical/max. ambient temp. -40/+25/+50°C. Built-in LED
is lit to indicate that the detector has activated a fire alarm.
Terminals for an ext. LED (2218).
6296 Heat detector: Enclosed (IP67)
S (static response temp. range 69-85°C), latching.
Min./typical/max. ambient temp. -40/+40/+65°C. Built-in LED
is lit to indicate that the detector has activated a fire alarm.
Terminals for an ext. LED ( 2218).
6297 Heat detector: Enclosed (IP67). Like 6295 but 87°C, class C S
(static response temp. range 84-100°C), latching.
Min./typical/max. ambient temp. -40/+55/+80°C. Built-in LED
is lit to indicate that the detector has activated a fire alarm.
Terminals for an ext. LED (2218).
6298 Heat detector: Enclosed (IP67). Like 6295 but 117°C, class E S
(static response temp. range 114-130°C), latching.
Min./typical/max. ambient temp. -40/+85/+110°C. No built-in
LED but terminals for an ext. LED (2218) - to indicate that the
detector has activated a fire alarm.
Accessories
3314 Address setting tool. Is used to write or read the units' COM
loop address (Technical address 001-127). It is also used to
write or read the mode, see the unit respectively. A connection
cable with crocodile clips and tab terminals is supplied with the
tool and can be used when required.
Put the ON/OFF switch in position ON and wait for a beep.
Plug the detector's SA & SB terminals onto the tool's SA & SB
terminals or, when required, use the connection cable.
How to read: Press "READ", wait for a beep and read the
address and mode.
How to write:
"READ" at the same time and/or write the address. Press
"WRITE" and wait for a beep. ("READ" again as a check.)
3390 Label holder. To be mounted in an analog base (3312 / 3312F /
32
3312FL / 4313)
29
This detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 100°C), -40°C < T
30
This detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 100°C), -40°C < T
31
Some units have flying leads for easier connection. After use they should
be disconnected and thrown away.
32
Also in an enclosed analog heat detector (3309).
29
Enclosed (IP67)
.
Fixed temperature heat
30
. Like 6295 but 72°C, class B
To select the mode, press "WRITE" and
. Intended for a label with "zone-address",
< 50°C.
a
< 65°C.
a
45
31