Connecting

4.6 Connecting I/Os

4.6
Connecting I/Os
Connection cables for the inputs/outputs of the D4x5‑2, CX32‑2, and TB30
For the input/output wiring, use rigid or flexible cables with a conductor cross-section as stated
in the manual.
Ferrules are not mandatory.
You can use ferrules without an insulating collar in accordance with DIN 46228, Form A long
version.
Note
To achieve optimum interference immunity, shielded cables must be used for connecting
analog signals, measuring inputs or external zero marks.
Tools required
Screwdriver 0.4 x 2.0 mm
Wiring inputs/outputs
1. Strip back the cable insulation as stated in the manual, if necessary, press on a ferrule.
2. Wire the digital inputs and outputs for connection of the sensors and actuators.
3. Insert the cable into the appropriate spring-loaded terminal. This is easier when you use
the screwdriver to push back the spring.
Additional references
For further information on cabling (e.g. use of rigid cables) and the pin assignment of the I/O
‑interfaces, see:
SIMOTION D4x5-2 Manual, Section "Digital inputs/outputs."
SIMOTION D4x5-2 Manual, Section "Controller Extension CX32‑2."
SIMOTION D4x5-2 Manual, Section "Digital inputs/outputs."
4.6.1

Creating a shield connection

Using shielded cables
The following options are available for the shield connection when using shielded cables:
● A shield connection using a shielding bus supplied separately
● Shield connection via shield connecting element on the top of the SIMOTION D4x5‑2/
CX32-2 housing
72
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B