Parameter assignment / addressing
6.3 Configuring PROFIBUS DP
Procedure
1. Open the project in SIMOTION SCOUT.
2. Click the "Open NetPro"
NetPro is accessed, and the configured network is graphically displayed. The PG/PC
connection to the configured network is shown in bold in a color other than yellow.
3. Double-click the PG/PC you would like to configure.
The "Properties - PG/PC" dialog will be displayed with the "Assignment" tab in foreground.
4. Select the interface in the "Assigned" field and activate S7ONLINE access by clicking the
appropriate checkbox.
5. Click "OK" to accept the settings.
The PG/PC connection to the configured network is displayed again in bold and yellow.
6. Save and compile the changes and download them to the SIMOTION D4x5‑2.
You can now go online via the PG/PC once again.
Alternatively, you can make the assignment in SIMOTION SCOUT by clicking the
PG/PC" button. This calls the properties window for PG/PC assignment, where you can modify
the assignment and "activate" it (S7ONLINE access).
142
button.
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
"Assign
SIMOTION D4x5-2