Parameter assignment / addressing
6.6 Configuring an Ethernet subnet
Assigning the Ethernet address later
It is possible to assign the IP address later on (e.g. on modular machines). In this case, an IP
address is not assigned in HW Config, but activated differently with the "Set IP address using
different method" option. The address will then be assigned later on the machine, for example,
by a the user program or by commissioning tools, such as PRONETA.
Further information on PRONETA can be found on the Internet:
● PRONETA: See Internet address
67460624)
6.6.3

Reading out IP and MAC address

Requirement
To read out the IP and MAC addresses, the following requirements must be met:
● SIMOTION D4x5‑2 is wired.
● You have assigned the communication parameters.
● You are online.
Procedure
The IP addresses and MAC addresses of SIMOTION D4x5‑2 can be displayed as follows via
SIMOTION SCOUT.
1. Right-click the module.
2. Select "Target device" > "Device diagnostics" in the context menu.
The addresses are displayed as follows, e.g. for SIMOTION D4x5-2 DP/PN:
X127 P1 (PN/IE)
● Active MAC Address: 08-00-06-73-25-3E
● IP address: 169.254.11.22
● Subnet mask: 255.255.0.0
● Standard gateway: No router used
X130 P1 (PN/IE‑NET)
● Active MAC address: 08-00-06-73-25-3F
● IP address: 192.168.2.1
● Subnet mask: 255.255.255.0
● Standard gateway: No router used