Error mes-
Description
sage
(hex)
0xE4FE8C
Communication error between Ident profile and communications module. Handshake error.
UDT of this communications module is overwritten by other program sections
Check parameter settings of communications modules in the UDT
Check the Ident profile command that caused this error
Start "INIT" after correcting the error
Backplane bus / Ethernet/IP error occurred
Execute "INIT"
0xE4FE8D
Internal communications error of the communications module/reader
Connector contact problem on the communications module / reader
Hardware of the communications module / reader has a defect; → Send in communications module
/ reader for repair
Start "INIT" after correcting the error
Internal monitoring error of the communications module/reader
Program execution error on the communications module / reader
Turn the power supply of the communications module/reader off and on again
Start "INIT" after correcting the error
0xE4FE8E
Active command canceled by "WRITE-CONFIG ("INIT" or "SRESET") or bus connector unplugged
Communication with the transponder was aborted by "INIT"
This error can only be reported if there is an "INIT" or "SRESET"
0xE5FE01
Incorrect sequence number order (SN) on the reader/communications module
0xE5FE02
Incorrect sequence number order (SN) in the Ident profile
Possible cause: User mode "RFID standard profile" is not set in the device configuration.
0xE5FE04
Invalid data block number (DBN) on the reader/communications module
0xE5FE05
Invalid data block number (DBN) in the Ident profile
0xE5FE06
Invalid data block length (DBL) on the reader/communications module
0xE5FE07
Invalid data block length (DBL) in the Ident profile
0xE5FE08
Previous command is active or buffer overflow
A new command was sent to the reader or communications module although the last command was still
active.
Active command can only be terminated with an "INIT"
Before a new command can be started, "DONE bit = 1" must be set; exception: "INIT"
Two Ident profile calls had the same "HW_ID", "CM_CHANNEL" and "LADDR" parameter settings
Two Ident profile calls are using the same pointer
Start "INIT" after correcting the error
When working with command repetition (e.g., fixed code transponder), no data is being fetched from
the transponder. The data buffer on the reader/communications module has overflowed. Transponder
data has been lost.
0xE5FE09
The reader or communications module executes a hardware reset ("INIT_ACTIVE" set to "1"). "INIT" is
expected from the Ident profile (bit 15 in the cyclic control word).
0xE5FE0A
The "CMD" command code and the relevant acknowledgement do not match. This can be a software error
or synchronization error that cannot occur in normal operation.
Ident profile, Add-on instruction for Rockwell systems
Function Manual, 01/2019, C79000-G8976-C410-03
5.2 Errors from the communications module/reader