Toshiba ACE-tronics G9 ASD Installation And Operation Manual page 94

Adjustable speed drive
Hide thumbs Also See for ACE-tronics G9 ASD:
Table of Contents

Advertisement

F011
Maximum Frequency
Program  Fundamental  Frequency
This setting determines the absolute maximum frequency that the ASD can
output.
Accel/Decel times are calculated based on the Maximum Frequency setting.
The Maximum Frequency is not limited by this setting while operating in the
Drooping Control mode (see
Note:
This setting may not be lower than the Upper-Limit Frequency
setting (F012).
Upper-Limit Frequency
Program  Fundamental  Frequency
This parameter sets the highest frequency that the ASD will accept as a
frequency command or frequency setpoint. The ASD may output frequencies
higher than the Upper-Limit Frequency (but, lower than the Maximum
Frequency) when operating in the PID Control mode, Torque Control mode,
or the Vector Control modes (sensorless or feedback).
Note:
This setting may not be higher than the Maximum Frequency
(F011)
setting.
Lower-Limit Frequency
Program  Fundamental  Frequency
This parameter sets the lowest frequency that the ASD will accept as a
frequency command or frequency setpoint. The ASD will output frequencies
lower than the Lower-Limit Frequency when accelerating to the lower limit or
decelerating to a stop. Frequencies below the Lower Limit may also be output
when operating in the PID Control mode, Torque Control mode, or the
Vector Control modes (sensorless or feedback).
Base Frequency 1
Program  Fundamental  Motor Set 1
The Base Frequency 1 setting is the frequency at which the output voltage of
the ASD reaches its maximum setting. The Base Frequency Voltage 1
parameter is set at F409.
For proper motor operation, the Base Frequency should be set for the
nameplate frequency of the motor.
84
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F320
for additional information on this setting).
Direct Access Number — F011
Parameter Type — Numerical
Factory Default — 65.0
Changeable During Run — No
Minimum — 30.0
Maximum — 299.0
Units — Hz
Direct Access Number — F012
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F013
Parameter Type — Numerical
Factory Default — 13.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper Limit (F012)
Units — Hz
Direct Access Number — F014
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Upper Limit (F012)
Units — Hz
ACE-tronics G9 ASD Installation and Operation Manual