F671
AM Output Terminal Adjustment
Program  Terminal  Analog Output Terminals
This parameter is used to calibrate the AM analog output.
To calibrate the AM analog output connect a voltmeter to the AM and CC
terminals.
With the ASD is running at a known value (e.g., output frequency), adjust this
parameter until the associated function of parameter
DC level output at the AM output terminal.
See
F670
for additional information on this setting.
MON1 Terminal Meter Selection
Program  Terminal  Analog Output Terminals
This parameter is used to set the output function of the MON1 analog output
terminal. The available assignments for this output terminal are listed in
on pg.
240.
The MON1 analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 Instruction Manual (P/N 58686) for
additional information on the function of this terminal.
MON1 Terminal Setup Parameters
F672
— MON1 Output Function
F673
— MON1 Terminal Meter Adjustment
F688
— MON1 Voltage/Current Output Switching
F689
— MON1 Output Gradient Characteristic
F690
— MON1 Bias Adjustment Set Zero Level
MON1 Terminal Meter Adjustment
Program  Terminal  Analog Output Terminals
This parameter is used to set the gain of the MON1 output terminal and is used
in conjunction with the settings of parameter F672.
See parameter
F672
for additional information on this setting.
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F670
produces the desired
Table 8
Direct Access Number — F671
Parameter Type — Numerical
Factory Default — 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Direct Access Number — F672
Parameter Type — Selection List
Factory Default — Output Voltage
Changeable During Run — Yes
Direct Access Number — F673
Parameter Type — Numerical
Factory Default — 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
F673
187