Toshiba ACE-tronics G9 ASD Installation And Operation Manual page 90

Adjustable speed drive
Hide thumbs Also See for ACE-tronics G9 ASD:
Table of Contents

Advertisement

F003
Command Mode
Program  Fundamental  Standard Mode Selection
The Command Mode Selection establishes the source of the command input
for the ASD. Command inputs include Run, Stop, Forward, etc. The
Override feature may supersede the Command Mode Selection setting (see
Command and Frequency Mode Control on pg.
Settings:
Terminal Board
EOI Keypad
RS485
Communication Option Board
Frequency Mode 1
Program  Fundamental  Standard Mode Selection
The Frequency Mode 1 setting establishes the source of the frequency-control
input for the ASD. The Frequency Mode 2 setting or the Override feature may
supersede the Frequency Mode 1 setting (see
Control on pg. 47
and
F200
Note:
Only bolded items from the Settings list below may be placed in
the Override mode.
Settings:
V/I
RR
RX
EOI Keypad
RS485
Communication Option Board
RX2 Option (AI1)
Option V/I
UP/DOWN Frequency
Pulse Input (Option)
Pulse Input (Motor CPU)
Binary/BCD Input (Option)
80
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
47).
Command and Frequency Mode
for additional information on this feature).
Direct Access Number — F003
Parameter Type — Selection List
Factory Default — Terminal Board
Changeable During Run — No
Direct Access Number — F004
Parameter Type — Selection List
Factory Default — RR
Changeable During Run — No
ACE-tronics G9 ASD Installation and Operation Manual
F004

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents