F210
RR Input Point 1 Setting
RR
Program  Frequency  Speed Reference Setpoints
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This parameter sets the RR input level that is associated with the RR Input
Point 1 Frequency setting when operating in the Speed control mode or is
associated with the RR Input Point 1 Rate (F214) setting when operating in
the Torque Control mode.
Speed Control
Perform the following setup to allow the system to perform Speed control from
the RR input terminal:
• Set RR Input Point 1 Frequency (F211).
• Set RR Input Point 1 Setting (F210) — the input analog signal level that
corresponds to the frequency setting at RR Input Point 1 Frequency.
• Set RR Input Point 2 Frequency (F213).
• Set RR Input Point 2 Setting (F212) — the input analog signal level that
corresponds to the frequency setting at RR Input Point 2 Frequency.
RR Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input
at the RR input terminal:
• Program  Fundamental  Standard Mode Selection  Frequency Mode
1  RR.
• Program  Fundamental  Standard Mode Selection  Command Mode
Selection  Terminal Board.
• Provide a Run command (F and/or R).
Once set, as the RR input voltage changes, the output frequency of the ASD
will vary in accordance with the above settings.
This parameter value is entered as 0% to 100% of the RR input signal range.
RR Input Point 1 Frequency
Program  Frequency  Speed Reference Setpoints
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control mode.
This parameter sets RR Input Point 1 Frequency and is the frequency that is
associated with the setting of RR Input Point 1 Setting (F210) when operating
in the Speed Control mode.
See RR Input Point 1 Setting (F210) for additional information on this setting.
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F210
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Frequency Settings
Direct Access Number — F211
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F211
113