D-3.6 Basic Application Functions - GE PACSystems RX3i User Manual

Iec 104 server module ic695eis001
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

Appendix D. Device Profile

D-3.6 Basic Application Functions

Station initialization
(station-specific parameter, mark 'X' if function is used)
Remote initialization
Cyclic data transmission
(station-specific parameter, mark 'X' if function is only used in the standard direction, 'R' if only used in the
reverse direction, and 'B' if used in both directions)
Cyclic data transmission
Read procedure
(station-specific parameter, mark 'X' if function is only used in the standard direction, 'R' if only used in the
reverse direction, and 'B' if used in both directions)
X
Read procedure
Spontaneous transmission
(station-specific parameter, mark 'X' if function is only used in the standard direction, 'R' if only used in the
reverse direction, and 'B' if used in both directions)
X
Spontaneous transmission
Double transmission of information objects with cause of transmission spontaneous
(station-specific parameter, mark each information type 'X' where both a Type ID without time and
corresponding Type ID with time are issued in response to a single spontaneous change of a
monitored object)
The following type identifications may be transmitted in succession caused by a single status change
of an information object. The particular information object addresses for which double transmission
is enabled are defined in a project-specific list.
X
Single-point information M_SP_NA_1, M_SP_TA_1, M_SP_TB_1 and M_PS_NA_1
X
Double-point information M_DP_NA_1, M_DP_TA_1 and M_DP_TB_1
X
Step position information M_ST_NA_1, M_ST_TA_1 and M_ST_TB_1
X
Bitstring of 32 bit M_BO_NA_1, M_BO_TA_1 and M_BO_TB_1
X
Measured value, normalized value M_ME_NA_1, M_ME_TA_1, M_ME_ND_1 and
M_ME_TD_1
X
Measured value, scaled value M_ME_NB_1, M_ME_TB_1 and M_ME_TE_1
X
Measured value, short floating point number M_ME_NC_1, M_ME_TC_1 and
M_ME_TF_1
80
PACSystems RX3i Ethernet 104 Server Module User Manual
(if defined for a specific project)
GFK-2949C