Parameter
mComreq_Setup[67]
mComreq_Setup[72]
GFK-2949C
Chapter 6. Configuration of IEC 104 Server Parameters Using COMMREQ
Value
Description
0 / 1
Bit 1 – When 1 SOE Disabled for M_SP
Bit 2 – When 1 SOE Disabled for M_DP
Bit 3 – When 1 SOE Disabled for M_ST
Bit 4 – When 1 SOE Disabled for M_BO
Bit 5 – When 1 SOE Disabled for M_ME_NA
Bit 6 – When 1 SOE Disabled for M_ME_NB
Bit 7 – When 1 SOE Disabled for M_ME_NC
[Note: The SOE events are generated only when the Controller is in
RUN I/O Enable state when the Bit 1 to Bit 7 is set to 1 for individual
ADSUs. If Bit 1 to Bit 7 are all set to 0, then SOE events are
generated irrespective of the Controller state (like STOP, Run Output
Disable, Run I/O Enable).]
Bit 8 – reserved
Bit 9 – reserved
The Firmware Release 1.40 and above provides enhancement to
enable Report by Exception of analog data without time stamp
through ASDU13 spontaneously instead of ASDU36, this
enhancement makes use of this bit as described below.
Bit 10 – When set to 1, M_ME_NC_1 (ADSU Type 13) - Measured
value, scaled value (Short Float) (without Time Tag) is sent as
"Spontaneous" or "RBE" response instead of M_ME_TF_1 (ADSU Type
36) - Measured value, scaled value with time tag CP56Time2a.
Bit 10 – Default is set to 0, In such case, M_ME_TF_1 (ADSU Type 36) -
Measured value, scaled value with time tag CP56Time2a is sent as
"Spontaneous" or "RBE" response and M_ME_NC_1 (ADSU Type 13) -
Measured value, scaled value (Short Float) (without Time Tag) is only
sent as response to "General Interrogation" or "Polling" command
from Client.
Bits 11 to 13 - Unused
Bit 14 – When 1: Do Not Mark Points as Substituted when point push
value is being used
Bit 15 – When 1: Do Not Mark Points as Non-Topical when CPU is in
STOP
Bit 16 – When 1: Do Not Mark Points as Non-Topical when CRU is not
Local Active
Integer
Queue Depth Override for Digital Points, 0 to 2000
If value is 0, then queue depth is set to 1024.
If value is greater than equal to 2000, then the queue depth is
clamped to 2000 by the EIS001 firmware.
July 2017
51