Option Parameters - GE PACSystems RX3i User Manual

Iec 104 server module ic695eis001
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

Chapter 6. Configuration of IEC 104 Server Parameters Using COMMREQ

6.4.5 Option Parameters

Parameter
mComreq_Setup[66]
50
Value
Description
0 / 1
Bit 1 – Clock Validity lasts for 1 hour
Bit 2 – Clock Validity lasts for 24 hours
*Note if Bit 1 and 2 are OFF, clock is valid forever; this is used when
there is a time synch to the Controller such as IRIG-B.
Bit 3 – Do Not accept time synch from a client
Bit 4 - 1 : CPU Time is taken for Event Time tagging
0 : EIS001 Module Time is taken for Event Time tagging
Bit 5 & Bit 6 – Multiple Client Connection Configuration