GE PACSystems RX3i User Manual page 56

Iec 104 server module ic695eis001
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

MSP Configuration
M_SP ADSU COMMREQ Configuration
Parameter
mComreq_Setup[18]
mComreq_Setup[19]
mComreq_Setup[20]
mComreq_Setup[21]
MDP Configuration
M_DP ADSU COMMREQ Configuration
Parameter
mComreq_Setup[22]
mComreq_Setup[23]
mComreq_Setup[24]
mComreq_Setup[25]
MST Configuration
M_ST ADSU COMMREQ Configuration
Parameter
mComreq_Setup[26]
mComreq_Setup[27]
mComreq_Setup[28]
mComreq_Setup[29]
Note: The step ranges from 0 to 63. The IEC 104 Client can step the ADSU object(s) from 0 to 63. The
step increment above 63 from IEC 104 Client does not result in the increment of value above 63. The
step decrement below 0 from IEC 104 Client does not result in the decrement of value below 0.
GFK-2949C
Chapter 6. Configuration of IEC 104 Server Parameters Using COMMREQ
Value
Description
m-type
Memory Type for SP Objects
value
Value: 70-%I, 72-%Q, 76-%M, 74-%T, 68-%G, 0-unused
address
Memory Address for ADSU object
value
Value: 1 to maximum (based on memory type)
Length
Number of ADSU Objects
CPO
Refer to Control Point Offset Configuration discussion in Section
6.4.4.
Value
Description
m-type
Memory Type for DP Objects
value
Value: 70-%I, 72-%Q, 76-%M, 74-%T, 68-%G, 0-unused
address
Memory Address for ADSU object
value
Value: 1 to maximum (based on memory type)
Length
Number of ADSU Objects
CPO
Refer to Control Point Offset Configuration discussion in Section
6.4.4.
Value
Description
m-type
Memory Type ST Objects
value
Value: 8-%R, 10-%AI, 12-%AQ, 196-%W, 0-unused
address
Memory Address for ADSU object
value
Value: 1 to maximum (based on memory type)
Length
Number of ADSU Objects
CPO
Refer to Control Point Offset Configuration discussion in Section
6.4.4.
July 2017
47