2.4.4
Installation area for an expansion rack
Confirm that the service areas (space used for maintenance) shown in
secured.
Figure 2-11 Example of service areas for an expansion rack (top view)
600 mm
(23.6 in.)
2.4.5
Bottom view of an expansion rack
Figure 2-12
and the casters on the bottom of the expansion rack. This top-view diagram shows
the bottom of the inside of the expansion rack as viewed from directly above.
Note that the values shown are expansion unit design values. To fix the leveling feet
to the floor, determine locations allowing for a tolerance of ±2 mm (±0.1 in.), which is
the dimensional tolerance of the expansion racks.
Fujitsu M10/SPARC M10 Systems Installation Guide ・ July 2015
34
Rear service area
Rack
Front service area
600 mm
700 mm
(23.6 in.)
(27.6 in.)
shows the locations of openings for taking out/in cables, the leveling feet,
Figure 2-11
900 mm
(35.4 in.)
1050 mm
(41.3 in.)
1200 mm
(47.2 in.)
are