Mitsubishi Electric GOT2000 Series User Manual page 183

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■2. Status of the GOT when it freezes (screen operation stopped)
(1) Check of switching to the utility screen
Check
Symptom
Possible
Impossible
(2) Executing the I/O check from the GOT utility
Check
Symptom
Communication error
No error
(3) Check of the objects that are not displayed on the monitor screen
Check
Symptom
Found
Not found
Cause/status
• Error code (system alarm):
Example:
460 Communication unit error
The system alarm cannot be used.
Cause/status
• Display details:
Example:
A message indicating that the cause
may be a connection error has been
displayed.
The hardware such as a
communication interface has no error.
Cause/status
• Details:
Example:
The numerical display object is not
displayed.
Corrective action
When the system alarm display function
can be used, take the action for the error
code (system alarm) displayed.
If the corrective action cannot be taken,
proceed to (2).
Proceed to (3).
Corrective action
Proceed to (3).
■ 3.
PLC status.
Proceed to
Corrective action
Proceed to ■3. PLC status.
10.1 GOT Restoration Sheets
10
10 - 5