Step 2.
Insert the GOT rear face into the panel opening. (The following shows an example of the horizontal
installation.)
Step 3.
Insert the hook of an installation fitting (supplied) into the mounting hole of the GOT.
Slide the installation fitting toward the GOT rear face.
Then, viewing from the GOT rear face, slide the fitting to the left to fix, and tighten a screw within the
specified torque range (0.20 N•m to 0.25 N•m).
Fix the GOT using 4 fittings at the top and the bottom of the GOT.
POINT
POINT
POINT
Cautions for the GOT installation
Tighten mounting screws within the specified torque range.
Undertightening can cause the GOT to drop.
In addition, waterproof effect or oilproof effect may not be obtained.
Tightening the screw in the specified torque range or more may damage the GOT or distort the
panel, causing wrinkles on the surface of the display section. The wrinkles may lower visibility
and lead to an incorrect input to the touch panel.
Waterproof effect or oilproof effect may not be obtained because of distortion of the GOT or
panel.
Step 4.
The GOT in the factory shipment state has a protective film on the display section.
After installing the GOT, remove the film.
Installation fitting
Mounting screw
1)
Panel opening
2)
3)
6.5 Installing and Removing the GOT