Conforming Standards In The Low Voltage Directive - Mitsubishi Electric GOT2000 Series User Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

Applied
standard
IEC61000-4-11
EN61131-2
Instantaneous power failure
: 2007
and voltage dips immunity
*1
The GOT is an open type device (designed to be integrated in equipment).
Make sure to install the GOT on a control panel.
This test item is conducted in the condition where the GOT is installed on a control panel and combined with the MITSUBISHI
PLC.
*2
QP: Quasi-peak value, Mean: Average value
*3
This test item is conducted in the following conditions.
• 30 MHz to 230 MHz
QP: 40 dBμV/m (measured at 10 m)
• 230MHz to 1000MHz
QP: 47 dBμV/m (measured at 10 m)
5.1.2

Conforming standards in the Low Voltage Directive

The GOT complies with the following standards in the Low Voltage Directive.
• EN61131-2: Programmable controllers - Equipment requirements and tests
• EN60950-1: Information technology equipment - Safety
Test standard
Test for checking normal operations at
instantaneous power failure
Test details
• AC power type
0.5 cycle 0% (Interval 1 second to 10
seconds)
250/300 cycle 0%
10/12 cycle 40%
25/30 cycle 70%
Standard value
5 - 3
5.1 Overview
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents