This zone type will arm and disarm the partition or partitions of the control panel where it is resident,
every time the zone is shorted. Keyswitch arming will report as User 99 in logs and reports. This zone
type can only belong to 1 partition.
INTERIOR FOLLOWER WITH "CROSS ZONE" ENABLED
12
This zone will be instant when the system is armed and no entry or exit delay is being timed. It is
delayed during entry and exit delay times. If a "Cross Zone" is not being timed, it will start a "Cross
Zone" timer. If a "Cross Zone" is being timed, it will create an instant alarm. This zone will bypass
automatically, when enabled in segment 1 of location 23.
13
INSTANT ENTRY GUARD
This zone creates an instant alarm whenever it is tripped and the zone is timed. It will start an entry
delay time 2 if it is tripped, provided that the system is armed and the stay/instant mode is on.
14
ENTRY/EXIT DELAY 1 WITH GROUP BYPASS ENABLED
A trip will start entry delay 1. This zone will bypass when the "Group Bypass" command is entered at the
keypad. Absence of a trip during exit delay will enable the automatic bypass or instant mode, if so
programmed.
15
INTERIOR FOLLOWER WITH GROUP BYPASS ENABLED
This zone will be instant when the system is armed and no entry or exit delays are being timed. It is
delayed during entry/exit delay times. This zone will bypass when the "Group Bypass" command is
entered at the keypad. This zone will bypass automatically, if enabled in segment 1 of location 23.
16
INSTANT WITH GROUP BYPASS ENABLED
This zone creates an instant alarm whenever it is tripped and the system is armed. This zone will
bypass when the "Group Bypass" command is entered at the keypad
17
MAINTAINED KEYSWITCH
This zone type will arm the partition or partitions of the control panel where it is resident, as long as the
zone is shorted. This zone type will disarm the partition or partitions of the control where it is resident,
as long as the zone is open. Keyswitch arming will report as user 99 in logs and reports.
ENTRY/EXIT DELAY 1 FORCE ARMABLE
18
A trip will start entry delay 1. Absence of a trip during exit delay will enable the automatic bypass or
instant mode, if so programmed. This zone is force armable, which means the system can be "Force
Armed" even if this zone has been violated. In this condition, the "Ready" icon will flash indicating the
zone is not secure. At the end of the exit delay, the zone will be bypassed. If the zone becomes secured
at any time during the arming cycle, it will be unbypassed and will become active in the system. If
"Bypass Report" is enabled, the force arming zones can be programmed to report bypass when they
are force armed (default).
ENTRY/EXIT DELAY 2 FORCE ARMABLE
19
A trip will start entry delay 2. Absence of a trip during exit delay will enable the automatic bypass or
instant mode, if so programmed. This zone is force armable (see description above).
ENTRY/EXIT DELAY 1 WITH CHIME ENABLED
20
A trip will start entry delay 1. Absence of a trip during exit delay will enable the automatic bypass or
instant mode, if so programmed. When the control panel is disarmed and the chime mode has been
set, this zone will act as a chime zone.
21
TECHNICAL ALARM, SUPERVISED, AUDIBLE
Any trip on a technical zone creates an audible alarm, regardless of the arming state of the control
panel. This zone can be bypassed.
22
TECHNICAL ALARM, SUPERVISED, SILENCE
Any trip on a silent technical zone creates a silent alarm, regardless of the arming state of the control
panel. Only the transmitter will be activated. This zone can be bypassed.
INTERIOR INSTANT ZONE
23
This zone creates an instant alarm whenever it is tripped during the arming state of the control panel.
This zone will bypass automatically, if enabled in segment 1 of location 23, or when this system is
armed in the "Stay" mode.
24
INSTANT ZONE WITH CHIME ENABLED
A trip will create an alarm when the system is armed. When the control panel is disarmed and the
chime mode has been set, this zone will act as a chime zone.
FOLLOWER ZONE WITH CHIME ACTIVATED
25
This zone will be instant when the system is armed and no entry or exit delays are being timed. It is
delayed during entry and exit delay times. This zone will not bypass automatically, even if enabled in
segment 1 of location 23. When the control panel is disarmed and the chime mode has been set, this
zone will act as a chime zone.
24 HOUR, AUDIBLE, SUPERVISED, LOCAL
26
NX-10 Installers manual
97