62 Electrical installation

Generator stator and generator cable

Check the insulation of the generator stator and cable as follows:
Check that all cables are disconnected from the converter output terminals U2, V2 and
W2.
Measure the insulation resistance between each phase conductor and the protective
ground conductor using a measuring voltage of 1000 V DC. The insulation resistance
of an ABB generator must exceed 100 Mohm (reference value at 25 °C (77 °F)). For
the insulation resistance of other generators, please consult the manufacturer's
instructions.
Note: Make sure that there is no condensed moisture inside the generator casing. If
you suspect that there is moisture, dry the generator before measurement.
Note: When using permanent magnet generator, it must be stable at the time of the
measurement.
ohm