This manual includes:
• ACS 600 initialisation using the Control
Panel
• First start
• Rotation direction check
• Start through a digital input
• Speed control using the Control Panel
and through an analogue input
ACS 600 Frequency Converters
equipped with Standard Application Program 5.x
Start-up Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB ACS 600

  • Page 1 ACS 600 Start-up Guide ACS 600 Frequency Converters This manual includes: • ACS 600 initialisation using the Control equipped with Standard Application Program 5.x Panel • First start • Rotation direction check • Start through a digital input • Speed control using the Control Panel...
  • Page 2 This Guide describes the basic start-up procedure of the ACS 600 frequency converter equipped with the Standard Application Program 5.x. See the Av…€h…rÃHhˆhyÃs‚…Ã68TÃ%ÃT‡hqh…qÃ6ƒƒyvph‡v‚Ã for more information on Q…‚t…h€Ã$‘à • the use of the Control Panel, • the control connections, • the Parameters, •...
  • Page 3 The ACx 600 must not be powered up more than five times in ten minutes to avoid charging resistor overheating (no limitation for ACS 600 MultiDrive and ACx 607 units -0760-3, -0930-5, -0900-6 or above).
  • Page 4: Start-Up Procedure

    [DTC] recommended • for multimotor drives when the number of motors connected to the ACS 600 is variable. • when the nominal current of the motor is less than 1/6 of the nominal current of the inverter. • when the inverter is used for test purposes with no motor connected.
  • Page 5 05 MOTOR NOM VOLTAGE Allowed range: 1/2 · U ... 2 · U of ACS 600. ( U refers to the highest voltage in each of the nominal voltage ranges: 415 VAC for 400 VAC units, 500 VAC for 500 VAC units and 690 VAC for 600 VAC units.) Nominal current.
  • Page 6 When the motor data has been entered a warning appears. -> 0.0 rpm It indicates that the motor parameters have been set, and the ACS 600 is ready to start the motor identification ** WARNING ** (ID magnetisation or ID Run). ID MAGN REQ Select the motor identification.
  • Page 7: Maximum Speed

    Start-up Guide START-UP PROCEDURE 5 – ROTATION DIRECTION OF THE MOTOR Check the rotation direction of the motor. L->[xxx] rpm FREQ xxx Hz • Press ACT to get the status row visible. CURRENT xx A • Increase the speed reference from zero to a small value POWER xx % by pressing REF and then...
  • Page 8: Application Macro

    Start-up Guide START-UP PROCEDURE 7 – STARTING THE DRIVE THROUGH THE I/O INTERFACE As default the external start/stop signal is read from the Valid if the factory macro is digital input DI1, and the external speed reference from the selected. See Parameter analogue input AI1.
  • Page 10 ABB Industry Oy Drives P.O.Box 184 FIN-00381 HELSINKI FINLAND Telephone: +358-10 22 2000 Telefax: +358-10-22 22681...