Samsung AE050RXYDEG Installation Manual page 39

Air to water heat pump
Hide thumbs Also See for AE050RXYDEG:
Table of Contents

Advertisement

Number of
Display contents
press
11
Fan RPM
Target discharge
12
temperature
13
EEV
14
Protective control
15
IPM temp .
long-1
Main Micom version
long-1 and 1 Inverter Micom version
long-1 and 2 EEPROM version
5 . Key Option
Option
Input unit
Channel address
Base heater
Operation mode
Snow accumulation
prevention control
Silent mode
Energy saving mode
Defrost Entry
Temperature Offset
• Incorrect handling of thermostat, safety valve or other valves may lead to tank rupture . When servicing the unit
follow instructions carefully:
WARNING
- Always turn off main power supply when water supply is being shut off .
- Test the free operation of the safety valve regularly by opening the valve ensuring the water flows freely .
- Electrical connection and all servicing of the electrical components should only be carried out by an
authorized electrician .
- Fitting and all servicing of plumbing fixtures should only be carried out by an authorized installer .
- When replacing the thermostat, safety valve or any other valve or part supplied with this unit, use only
approved parts of the same specification .
Segment 1
B
C
D
E
F
Year(Dec)
Year(Dec)
Year(Dec)
SEG1
SEG2
Main
0
0
Main
0
1
Main
0
2
Main
0
3
Main
0
4
Main
0
5
Main
0
6
ENGLISH-39
Display
Segment 2
Segment 3
1000s digit
100s digit
100s digit
10s digit
1000s digit
100s digit
Protective control
0 : No protective
control
1 : Freezing
0 : Cooling
2 : Defrosting
1 : Heating
3 : Over-load
4 : Discharge
5 : Total current
+/-
10s digit
Month(Hex)
Day(two digit)
Month(Hex)
Day(two digit)
Month(Hex)
Day(two digit)
SEG3
SEG4
A
U
Automatic address setting (default)
0
0
Manual address setting (0 to 15)
0
0
0
1
0
0
0
1
0
0
0
1
0
0
0
1
Manual Silent mode * 0 . 9 (-5 dB)
0
2
Manual Silent mode * 0 . 7 5 (-7 dB)
0
3
0
4
Low-noise Silent mode (default)
0
0
0
1
Defrost entering temperature = Default
0
0
Defrost entering temperature = Default+1°C
0
1
0
2
Defrost entering temperature = Default+2°C
0
3
Defrost entering temperature = Default+3°C
Units
Segment 4
10s digit
rpm
1s digit
10s digit
step
Frequency status
0 : Normal
1 : Hold
2 : Down
3 : Up_limit
4 : Down_limit
1s digit
Day(One digit)
Day(One digit)
Day(One digit)
Function of the option
Enabled (default)
Disabled
Heat Pump (default)
Heating Only
Disabled (default)
Enabled
Manual Silent mode (-3 dB)
Manual Silent mode (-3 dB)
Disabled (default)
Enabled
°C
-
°C
-
-
-