Piping work
Flow sensor
Flow sensor is not integrated part in MONO Unit . But the installation is essential to operate MONO Unit .
Flow sensor is provided by Samsung control kit as a sub component .
• Flow sensor shall be installed described by installation manual of Mono unit or Control kit .
• All electric wiring works shall be implemented by manuals which Samsung provided .
CAUTION
• Before completing the installation works, make sure to check if the flow sensor is installed in horizontal or
vertical like as below figure .
• If flow direction is in parallel with pipe direction . Straight length of In pipe of flow sensor shall have 10 times
length in diameter and Straight length of Out pipe of flow sensor shall have 5 times length in diameter .
• When mechanical vibrations are delivered from the pump or compressor, measurement errors may occur . Select
the installation location so that no vibrations are delivered to the sensor .
- Possibility of drain-off
- Possibility of bubble formation
min . 10 pipe in diameter
- Possibility of bubble formation
- Possibility of drain-off
(measuring pipe partly filled)
min . 5 pipe in diameter
ENGLISH-28
- No dager due to accumulation of contaminants
- Air bubbles goes upstream