Piping work
Freeze protection
Freeze protection solutions must use propylene glycol with a toxicity rating of Class 1 as listed in Clinical Toxicology of
Commercial Products, 5th Edition .
• Ethylene glycol is toxic and must not be used in the primary water circuit in case of any cross-contamination of
the potable circuit .
WARNING
Percent Propylene Glycol [wt. %]
0
10
20
30
36
40
43
48
Setting capacity and pre-pressure of the expansion vessel
When it is required to change the default pre-pressure of
the expansion vessel(1 bar), keep in mind the following
guidelines:
f Use only dry nitrogen to set the expansion vessel pre-
f
pressure .
f Inappropriate setting of the expansion vessel
f
pre-pressure will lead to malfunction of the system .
Therefore, the pre-pressure should only be adjusted by a
licensed installer .
Installation height
difference(a)
<7m
No pre-pressure adjustment required .
Actions required:
• Pre-pressure must be increased, calculate the
appropriate value following by "Calculating
>7m
the pre-pressure of the expansion vessel" .
• Check if the water volume is lower than
maximum allowed water volume .
(a) Installation height difference: height difference(m) between the highest point of the water circuit and the indoor unit . If
the unit is located at the highest point of the installation, the installation height is considered 0m .
• When Expansion vessel has a capacity 8 liters and 1bar pre-charged .
Water volume of total system for reliable performance is minimum 30 liters .
Freezing Points of Propylene Glycol - Water Mixtures
Freezing Point [ °F ]
32
26
20
10
0
-5
-10
-20
< 220 Litres
ENGLISH-26
2.5
2.0
1.5
Operation range
1.0
0.5
0.0
150
200
Total water volume(ℓ)
Water volume
Actions required:
• Pre-pressure must be decreased, calculate
according to "Calculating the pre-pressure of
the expansion vessel" .
• Check if the water volume is lower than
maximum allowed water volume .
Expansion vessel of the unit too small for the
installation .
Freezing Point [ °C ]
0
-3
-7
-12
-18
-20
-23
-29
250
300
> 220 Litres