When installing more than 1 outdoor unit
❋ ❋ When the air outlet is towards the wall
300 or more
600 or more
❋ ❋ When 3 sides of the outdoor unit are blocked by the wall
600 or more
❋ ❋ When front and rear side of the outdoor unit is towards the wall
1500 or more
600 or more
❋ ❋ When front and rear side of the outdoor unit is towards the wall
• The units must be installed according to distances declared, in order to permit accessibility from each side, either
to guarantee correct operation of maintenance or repairing products . The unit's parts must be reachable and
CAUTION
removable completely under safety condition (for people or things) .
600 or more
600 or more
600 or more
3000 or more
3000 or more
ENGLISH-19
300 or more
300 or more
❋ ❋ The upper part of the outdoor unit and the
air outlet is opposite the wall
300 or more
(Unit : mm)