8.15 Reversing with Two Line Contactors

Notes:
A N.O. auxiliary contact in each of the two line contactors C1 & C2 controls the START/STOP command.
Closure of either contactor will supply main power and a start signal to the ASTAT-XT.
It is recommended to employ a mechanical interlock between the forward and reverse contactors.
It is required to delay the transfer between opening of one contactor and closing of second contactor.
Phase Sequence fault must be disabled to operate reversing contactors at the line input of the
ASTAT-XT. Refer section 4.7.7 page 38 for programming.
• Application diagrams