Overview Of All Mode Pages And Factory Defaults - GE ASTAT XT QT 0008U Series User Manual

Solid state soft starter
Table of Contents

Advertisement

Overview of All Mode Pages and Factory Defaults

4.7
Display Page
Main Settings
Function & Default
Function & Default
Motor Current
Starter Current
0
58 AMP.
Line Voltage
Motor Current
0 Volt
58 AMP.
Thermistor Input.
LINE/DELTA Conf.
3.1 Kohm
Line
Undercurrent FLT
0% of Im
Undercurrent DLY
10 SEC.
O/C JAM Fault
850% OF Im
O/C JAM Delay
0.5 Sec.
Overload Class
IEC CLASS 10
Overload Protect
Enabled
Undervoltage FLT
300 Volt
Undervoltage DLY
5 SEC.
Overvoltage FLT
480 Volt
Overvoltage DLY
2 SEC.
Store Settings
Main
Refer to section 5.5.1 on page 49 for changing mode from Minimized Mode to Maximized Mode.
16
24
Start Settings
- **** -
-
- ****
Function & Default
Soft Start Curve
0(Standard)
Kickstart Time
0 SEC.
Starting Voltage
30 %
Starting Current
100 %
Current Limit
400% OF Im
Ramp UP Time
10 SEC.
Max. Start Time
30 SEC.
Number of Starts
10
Duty Cycle Time
30 Min.
Start Lockout
15 Min.
EOR Relay Delay.
5 Sec.
Store Settings
Start Settings
Settings
• Control Keypad
Stop Settings
- **** -
Function & Default
Soft Stop Curve
0(Standard)
Ramp DOWN TIME
10 SEC.
End Torque
0 (MIN.)
Store Settings
Stop Settings
Appears only in
Maximized
16
DUAL Settings
Parameters
Function & Default
Starting VOLT-2
30%
Starting CURR-2
100%
Current Limit-2
300% of Im
Ramp UP-2
10 SEC.
Ramp DOWN-2
10 SEC.
Motor Current-2
31 AMP.
Store Settings
Dual Settings

Advertisement

Table of Contents
loading

Table of Contents